All Collections
Troubleshooting
AMBR App
Reset your AMBR to DHCP, Static, or Factory Defaults
Reset your AMBR to DHCP, Static, or Factory Defaults
Sebastien Gouin-Davis avatar
Written by Sebastien Gouin-Davis
Updated over a week ago

Issue

My router is set in the wrong mode and I cannot log into my AMBR app, I need to switch from static to DHCP or vice versa.

Troubleshooting

We highly recommend using the AMBR app to modify network settings. If you cannot access your AMBR app because your network config settings are unknown or incorrect, follow the steps below.

AMBR_Backside-01.png

Before proceeding, keep in mind:

  • It is okay if you over-press Button B, continue to press it until the LED matches the mode you are expecting.

Step 1: Enter config mode

  • Press and hold the B button for 3 seconds. After three seconds, the White LED will begin to blink. Release the B button.

Step 2: Select one of the following options on your AMBR device

At this point the following options are available, by pressing and releasing the B button to cycle through the choices:

  • DHCP: Press and release the B button once to select the DHCP option. The Blue LED will display solid to indicate this choice.

  • STATIC IP: Press and release the B button a second time to select the Static IP option. The Orange LED will display solid to indicate this choice. Static values will be set to the following:

    IP address: 192.168.5.241

    Subnet: 255.255.255.0

  • FACTORY RESET: Press and release the B button a fourth time to select the factory reset option. The Blue, Yellow, and Green LEDs will all display solid to indicate this choice. This will delete any user created profiles, as well as the password if it was changed from the default. Please note that this also deletes the profile that is shipped with the unit. This is the profile named for the Device ID of the router.

    Warning: You will also have to factory reset your devices if your site is commissioned. If you have sensors in your site, please email support@amatiscontrols.com before conducting the factory reset.

  • EXIT WITH NO CANGES: Press and release the B button a third time to select the “Exit Config with out changes” options. The Green LED will display solid to indicate this choice.

Step 3: Apply selection

  • For DHCP, Static, or Exit with No Changes: press and hold the B button for 3 seconds to commit to the choice.

  • For a Factory Reset: press and hold the B button for 15 seconds. All LEDs will blink to indicate that you are about to reset the unit. Then press and hold the B button for another 15 seconds to confirm that is what you want to do. The LMBR-650 will then reboot.NOTE: If you are on option 4 and press and release the B button without holding it for the 15 seconds, the unit will cycle back to choice 1, as indicated by the LEDs.

Did this answer your question?