False Alarm Management – Advanced Panels

False Alarm Management with Advanced Panels.

Updated yesterday

Step 1:

Select the 'False Alarm Management' icon under 'Alarm Verification' the method is not selected.

Step 2:

Select type 'B' method -- the verification time will be defaulted to 240 second and all the smoke detectors are added by default.

If Heats and Multi's need to be added, change the '-' to 'ALL' using the drop-down menu. Under 'Verification Outputs', change the 'ALL' to '-' on the sounders and beacons.

All devices will now have a verification time of 240 seconds -- I.E., the fire condition will need to be persistent for this duration.

Contact Information
For further assistance or if you have any questions regarding this procedure, please contact the Eurotech Technical Team: