Equipment Details

Connection

RevPi modules connection through the electronic module

RevPi local network connection (protected side)

RevPi cloud connection (unsecured side)

WARNING : For a USB connection, please ensure that the switch (encircled below) is on the USB side.

Connecting RevPi Modules to the Power Supply

To connect the power supply to your RevPi Core, follow these steps :

Step 1 : Locate the X4 Connector (encircled below) : The X4 connector is specifically designed for powering the RevPi Core module and any connected devices.

Step 2 : Prepare the Power Supply :

Ensure you have a power supply unit that provides at least 11 W. You also need wiring with a cross-section between 0.35 mm² and 2.5 mm² (AWG22 to AWG14).

Step 3 : Make the Connections :

  • Connect terminal 1 on the X4 connector to the positive pole (24 V) of your power supply.

  • Connect terminal 2 to the negative pole (0 V or ground) of the power supply.

Step 4 : Optional Earth Connection : Terminal 4 is an optional functional earth. Connecting it can improve the system’s electromagnetic compatibility (EMC), although it’s not required.

Step 5 : Secure the Connections : Double-check that all connections are secure to ensure stable and reliable power delivery.