The following guide describes how to configure the Modbus TCP settings for SMA inverters and how to test the connection.

Prerequisites

Required Items

  • WiFi-capable device (smartphone, tablet, or laptop)

  • Inverter serial number

  • WPA2-PSK password (located on inverter label)

  • Installer rights for certain settings

Configuration Process

Initial Connection

Choose one of these connection methods:

WiFi Connection

  1. Find network named SMA19xxxxxxx

  2. Use IP address: 192.168.12.3

Ethernet Connection

  1. Connect via ethernet cable

  2. Use IP address: 169.254.12.3

Settings Configuration

  1. Open web browser

  2. Enter appropriate IP address based on connection method

  3. Log in as Installer

  4. Navigate to Device Parameters

  5. Select Edit Parameters

Modbus Setup

  1. Navigate to Modbus settings

  2. Enable the Modbus feature

  3. Enable TCP server

  4. Leave the port as 502

Grid Connection Configuration

For standard models:

  1. Go to System and device control

  2. Find Grid connection point

  3. Change Operating mode of active power limitation to External

For SBx.x-1AV40/41 models:

  1. Locate Operating mode active power setting

  2. Set to External active power setpoint

Finalizing Changes

  1. Always click Save All after making modifications

  2. Wait for changes to be applied

Troubleshooting

Modbus Setting Issues

If unable to change Modbus settings:

  1. Contact your installer

  2. Check if settings are locked by SMA Grid Guard

  3. Verify installer access rights

Connection Problems

If experiencing connection issues:

  1. Verify correct WiFi network selection

  2. Double-check IP address

  3. Ensure you're within range of the inverter

Missing Settings

If settings are not visible:

  1. Verify your model number

  2. Check for alternative setting names

  3. Confirm installer access level

Testing Connectivity (advanced)

After enabling Modbus TCP on your SMA inverter, you should verify that the connection is functioning correctly. You can follow our testing guide to confirm the connection. For SMA inverters, use the default Modbus port 502. The Unit ID is typically set to 3, which differs from many other manufacturers. Make sure you've completed all the grid connection configuration steps before testing, as these settings can affect Modbus communication.